变流量系统中送风温度的优化设计(英文)
In a variable air volume (VAV) system with 100% outdoor air, the cooling need in the building is satisfied with a certain air flowat a certain
supply air temperature. To minimize the system energy use, an optimal supply air temperature can be set dependent on the load, specific
fan power (SFP), chiller coefficient of performance, outdoor temperature and the outdoor relative humidity. The theory for an optimal
supply air temperature is presented and the heating, ventilation and air-conditioning (HVAC) energy use is calculated depending on supply
air temperature control strategy, average U-value of the building envelope and two outdoor climates. The analyses show that controlling
the supply air temperature optimally results in a significantly lower HVAC energy use than with a constant supply air temperature. The
optimal average U-value of the building envelope is in practise mostly zero.
© 2003 Elsevier B.V. All rights reserved.